EARTH BONDS FOR USE
WITH STEEL PLATE

These earth bonds provide both electrical and mechanical connection on an earth wire to a steel structure.

They consist in a pre-assembled tinned copper bush with a stainless steel dowel.

Drill a hole

Set the bond

Connection
Plates
Steel - Stainless steel
Plate thickness
1.5 - 4mm
2 - 4 mm
> 4 mm
> 4 mm
Earth bond thread
M6
M10
M6
M10
Ptnb
80923
80924
80925
80926
Drilling diameter
11.5 mm
19 mm
8.5 mm
13.5 mm
Setting tool
PMT6
PMT10
PMT6
PMT10
Tightening torque
6 Nm
30 Nm
6 Nm
30 Nm
Plans

ELECTRICAL PERFORMANCE

Ptnb
80923
80924
80925
80926
Electrical resistance measured between the terminal lug and the steel plate (thickness)
25 µOhm
(2 mm)
20 µOhm
(2 mm)
25 µOhm
(4 mm)
20 µOhm
(4 mm)
Electrical resistance measured between the terminal lug and the stainless steel plate (thickness)
120 µOhm
(2 mm)
70 µOhm
(2 mm)
75 µOhm
(4 mm)
60 µOhm
(4 mm)
The earth bond has passed 3 short circuit tests on both 2 mm steel and stainless steel plate with no degradation of the connection
10 kA
15 kA
10 kA
20 kA
Corrosion test :
The electrical resistance after 500 hours salt spray test remains lower than :

- on 2 mm steel plate
30 µOhm
25 µOhm
--
--
- on 2 mm stainless steel plate
150 µOhm
90 µOhm
--
--

MECHANICAL PERFORMANCE

Ptnb
80923
80924
80925
80926
Tensile load test :
The earth bond connection can accept a tensile load of :
(plate thickness)
400 daN
(2 mm)
500 daN
(2 mm)
500 daN
(4 mm)
800 daN
(4 mm)
Pressure seal :
Pressure load applied for 2 hours with no air leak between the earth bond and plate :
6 Bar
6 Bar
6 Bar
6 Bar
Terminal lug rotation test :
Rotation torque applied to the terminal lug with no rotation of the self locking nut or the earth bond :
7 Nm
35 Nm
10 Nm
20 Nm